BCM-201-FS5 Series Combustion Controller

BCM-201-FS5 Series Combustion Controller

Sample out chain download
Product Feature
For direct ignition or two-stage ignition
Internal parameters can be modified
Can be started locally or remotely
After ignition, the ignition valve remains open or closed, which can be set through parameters
By default, it is equipped with a communication interface, which can simultaneously control 100 controllers and read the required status information through communication
Flame intensity and alarm information display
IP64, can be installed independently without a control cabinet
Purge waiting time can be set, and the purge function requires an external circuit (0-250s)
Automatic ignition frequency can be set after ignition failure (0-4 times)
The flame response time can be set (1-12 seconds)
The ignition safety time can be modified, but it must comply with local standards
Flame sensitivity can be set (1-9ua), with a default of 2ua
The waiting time for rear blowing can be set (0-250s)
WhatsApp
Email
Message
Top
Contact Us
Product Inquiry
Service Support
Partnership Consultation
Leave A Message For Consultation
We welcome anyone to contact us. Please describe your question, and our team will get back to you within 2 business days.
We promise to collect this information from you only for the purpose of contacting you and helping you better understand our cooperation program. By sending, you agree to our 《Privacy Policy》.